Induced-draft A-frame condenser: a regression pin with no published answer

Tier 3: CFD, co-simulation or another model.

System: Air-cooled condenser, A-frame induced draft

What was compared
The air mass flow rate, the heat transfer rate, the steam condensed, the fan shaft power, the air outlet temperature and the total oblique-flow loss coefficient of an induced-draft A-frame air-cooled condenser unit with the delta and fan of Kröger's Example 8.1.4.
Against
No published reference exists, since Kröger gives no induced-draft A-frame example; every row is the model's own recorded solution. The two halves of the calculation are compared separately: the induced-draft equation (Kröger, Eq. 8.1.17) in Kröger's Example 8.1.2, and the delta and its fan in Kröger's Example 8.1.4.
The agreement
No agreement with an independent source is claimed. The rows hold the model's own solution to within 0.05%: an air mass flow rate of 542.6 kg/s, a heat transfer rate of 18.29 MW and a shaft power of 162 kW per fan.
What it shows
The case detects a change in the model's result for this system and says nothing about its accuracy. The accuracy of the induced-draft A-frame unit rests on Kröger's Examples 8.1.2 and 8.1.4, which verify its two halves separately.
Source
This model, gated against the two halves Kröger does publish: Eq. 8.1.17 as Example 8.1.2 and the delta as Example 8.1.4No published example exists; Kröger publishes no induced-draft A-frame unit.