Bekker et al. 2022

The induced-draft bank under wind, along and across its axis

Tier 3: CFD, co-simulation or another model.

System: Air-cooled condenser, A-frame induced draft

What was compared
The volumetric and thermal effectiveness of a five-by-four induced-draft A-frame air-cooled condenser bank under a wind of 3, 6 and 9 m/s along and across its long axis, and the flow on its wind-facing periphery at 9 m/s.
Against
The CFD study of Bekker et al. (2022, Section 3.3) in OpenFOAM, which reports the 20-unit means to the nearest 1%; it is a second model and not a measurement.
The agreement
Every published row is reproduced within the case's tolerance of ±0.5%. The agreement holds by construction, because the model's wind method for an induced-draft bank is calibrated on these six points.
What it shows
The case verifies that the model carries the study's series, interpolates it linearly in wind speed and blends the two directions by cos2 and sin2; the 45° row is the model's own. It is a self-consistency check and not independent evidence for the effect of wind on an induced-draft bank.
Source
G.M. Bekker, C.J. Meyer, S.J. van der Spuy, 'Influence of pressure recovery on the performance of an induced draught air-cooled condenser under windless and windy conditions', Applied Thermal Engineering 213 (2022) 118703Section 3.3 (wind along and across the ACC), Tables 2 and 4 for the geometry