Dong et al. 2021

The Gatton tower's steady end-state, from a second campaign

Tier 2: measurement on a controlled rig.

System: Indirect dry cooling, natural draft, horizontal array

What was compared
The steady state of the 20 m Gatton natural-draft dry cooling tower with a horizontal array, windless, at a burner input of 845 kW and a water flow of 15 kg/s: the water temperatures, and the heat transfer rate the model gives at the measured water inlet temperature.
Against
Measurements on the operating tower by Dong et al. (2021, Section 3.1, Fig. 4 and Table 1), with stated sensor uncertainties (±2.82% on the heat transfer rate). The steady water temperatures are read off a figure and agree with the independent campaign of Li et al. (2017, Table 3) to 0.1 K on the inlet.
The agreement
The model over-predicts the heat transfer rate by 25.8% with its default air-side relations and by 12.3% with the paper's own bundle loss coefficient, both far outside the measurement uncertainty.
What it shows
The case records the size of the model's error on a small tower whose in-line bundle differs from the staggered bundles every available air-side relation was fitted to; it is refused for model-form uncertainty and validates no relation on this bundle. It also holds the only measured repeatability in the catalogue: two campaigns on the tower differ by 0.1 K on the water inlet temperature and 0.4 K on the outlet.
Source
P. Dong, X. Li, Z. Guan, H. Gurgenci, L. Zhang, J. Feng, 'Starting up a practical natural draft cooling system: Experimental and theoretical study on transients', International Communications in Heat and Mass Transfer 126 (2021) 105444Section 3.1, Fig. 4 and Table 1; the windless 15 kg/s test.