A 112-cell air-cooled condenser under crosswind to 12 m/s: the extrapolation's size

Tier 3: CFD, co-simulation or another model.

System: Air-cooled condenser, A-frame forced draft

What was compared
The fan volume flow rate of a 112-cell A-frame air-cooled condenser under crosswind at 2 to 12 m/s, relative to its windless value, for the whole condenser and for the windward fan row.
Against
The CFD study of a 2 x 600 MW direct air-cooled condenser by He et al. (2013, Section 4.2 and Fig. 6), digitised; another model and not a measurement.
The agreement
At 2 m/s the whole-condenser flow ratio agrees to within 0.2 points (0.982 against 0.98). The model reads 3.8 points high at 4 m/s and 11.3 and 12.3 points high at 8 and 12 m/s (0.963 against 0.85 and 0.84), and its windward-row factor stays at 0.786 above 3 m/s where the CFD's falls to 0.57 at 12 m/s.
What it shows
The case measures how far the crosswind method of Kröger (Vol. 2, Section 9.3) departs from a CFD study when it is extrapolated beyond the 3 m/s its tabulated factors cover. It records the size of that extrapolation and is not evidence of accuracy at those wind speeds.
Source
W. He, L. Yang, X. Du, Y. Yang, 'Performance prediction of an air-cooled steam condenser using UDF method', Appl. Therm. Eng. 50 (2013) 1339-1350Section 4.2 and Fig. 6 (fan flows against wind speed), Table 3 (back pressure)