Kröger Example 8.1.2

Induced-draft air-cooled heat exchanger bay

Tier T: a textbook worked example - a published answer, not a measurement.

System: Air-cooled heat exchanger, induced draft

What was compared
The air mass flow rate, the heat transfer rate, the fan shaft power, the air outlet temperature and the overall conductance of an induced-draft bay of two fans above two six-row bundles cooling a process fluid.
Against
Kröger's worked Example 8.1.2 (Kröger, Vol. 2, Section 8.1), a published calculation and not a measurement.
The agreement
The air mass flow rate is reproduced to within 0.10%, the heat transfer rate and the fan shaft power to within 0.04%, and every temperature to within 0.04 K.
What it shows
The agreement verifies that the model implements Kröger's draft equation for an induced-draft bay (Kröger, Eq. 8.1.17) and his fan representation on the heated air as published. It says nothing about the method's accuracy against a measured plant.
Source
Kröger, D.G., Air-Cooled Heat Exchangers and Cooling Towers: Thermal-Flow Performance Evaluation and Design (PennWell, 2004)Vol. 2, Example 8.1.2