An eighteen-unit air-cooled condenser bank

Tier T: a textbook worked example - a published answer, not a measurement.

System: Air-cooled condenser, A-frame forced draft

What was compared
The inlet flow ratio, the plan dimensions, the heat transfer rate and the recirculation effectiveness of a bank of eighteen forced-draft A-frame condenser units in three rows of six, on a platform 25 m above ground behind an 8.27 m windwall.
Against
Kröger's worked Examples 8.3.2 and 8.4.2 (Kröger, Vol. 2, Sections 8.3 and 8.4), which extend the unit of Example 8.1.4; they are published calculations and not measurements.
The agreement
The inlet flow ratio of 0.98398 and the bank's plan width and length are reproduced exactly, and the bank's flow-proportional heat transfer rate of 347.68 MW to 0.004%. The recirculation effectiveness is 0.99185 against the printed 0.99139, within the case's tolerance of ±0.1%; the printed value does not follow from the example's own inputs, which give 0.99116.
What it shows
The agreement verifies that the model implements Salta and Kröger's inlet flow ratio (Kröger, Eq. 8.3.2) and Duvenhage and Kröger's recirculation correlation (Eq. 8.4.25) for a forced-draft condenser bank as published. Neither relation states an accuracy, and the agreement says nothing about their accuracy against a measured bank.
Source
Kröger, D.G., Air-Cooled Heat Exchangers and Cooling Towers: Thermal-Flow Performance Evaluation and Design (PennWell, 2004)Vol. 2, Examples 8.3.2 and 8.4.2 (both extending Example 8.1.4), §8.3 Eq. 8.3.2 and §8.4 Eqs. 8.4.10-8.4.25