Kröger Example 9.3.1

The six-bay bank under a 3 m/s crosswind

Tier T: a textbook worked example - a published answer, not a measurement.

System: Air-cooled heat exchanger, forced draft

What was compared
The heat transfer rate of the six-bay forced-draft bank of Kröger's Example 8.3.1 under a crosswind of 3 m/s at 5.7 m across its long axis, with the mean fan flow ratio and the recirculation effectiveness under that wind.
Against
Kröger's worked Example 9.3.1 (Kröger, Vol. 2, Section 9.3), which reads its factors from the CFD study of Duvenhage and Kröger (1996); a published calculation and not a measurement.
The agreement
The model gives a mean fan flow ratio of 0.917 against Kröger's 0.9 and a recirculation effectiveness of 0.967 against his 0.97, and the heat transfer rate of the bank comes out 1.5% above his 65.355 MW. The differences are Kröger's rounding of his figure readings, and every row lies within its tolerance: 2% on the heat transfer rate, 3% on the flow ratio and 1% on the effectiveness.
What it shows
The agreement verifies that the model implements Kröger's crosswind procedure for a fan-driven bank, reading the factors of Duvenhage and Kröger as he does. The factors come from a CFD study of a smaller bank applied beyond its range, and the case says nothing about the procedure's accuracy against a measured bank.
Source
Kröger, D.G., Air-Cooled Heat Exchangers and Cooling Towers: Thermal-Flow Performance Evaluation and Design (PennWell, 2004)Vol. 2, Example 9.3.1 (extending Example 8.3.1), Figs. 9.3.6-9.3.11 after Duvenhage and Kröger (1996)