Wei's wind tunnel on a Heller ring: the pressure coefficients want 0.62, the heat-side correction wants nothing

Tier 2: measurement on a controlled rig. Used at Tier 3, because its source states no uncertainty.

System: Indirect dry cooling, natural draft, vertical bundles

What was compared
The wind effect coefficient Cw, the fractional change in the heat transfer rate with wind, of a ring of standing radiator segments around the inlet of an indirect natural-draft tower, and its throat pressure coefficient, each against the ratio of the wind speed to the radiator velocity.
Against
Wind-tunnel measurements by Wei et al. (1995, Figs. 8, 9 and 11) on a 1/200 Froude-matched model of the Shanxi tower with heated radiators, a physical model with no stated measurement uncertainty.
The agreement
As printed, Kröger's crosswind method over-predicts the loss three- to fourfold: Cw is −20% at a velocity ratio of 2 and −30% at 3.2, against the measured −5.0% and −8.9%. With the heat transfer correction for wind αQ forced to 1, a multiplier of 0.615 on the pressure coefficients reproduces the measured curve over ratios of 1 to 4 to 1.26 points RMS, and the ring default of 0.5 to 1.8 points RMS.
What it shows
The case indicates that the draft side of the method transfers to a ring when its pressure coefficients are scaled by 0.5 to 0.6, as in the product's ring default of 0.5, and that the heat-side correction (Kröger, Eq. 9.2.10), which the default leaves unchanged, does not. The radiator, the water conditions and the site of the tower are declared, not measured.
Source
Q. Wei, B. Zhang, K. Liu, X. Du, X. Meng, 'A study of the unfavorable effects of wind on the cooling efficiency of dry cooling towers', Journal of Wind Engineering and Industrial Aerodynamics 54/55 (1995) 633-643Section 2 (the full-scale tower), 3.1 (similarity, the Froude number), 3.2 (models I and II), 4.1 and Fig. 8/9 (Cw), 4.3 and Fig. 11 (throat Cp)